4-12 Connecting the Network Interface Card
Publication 1784-UM527B-EN-P - October 2003
Table 4.1 Selecting the External Resistor
Interpreting the Status LEDs
What the LEDs mean depends on which protocol is running. Only the PKTXD uses both
LEDs. The left LED (labeled |) is for the top channel on a PKTXD and the other is for the
second, lower channel. A PKTX has only one channel (but multiple connectors depending on
protocol) so only one LED is used.
Table 4.2 explains the DH+ Status LED. Table 4.3 on page 4-13 explains the DH-485 Status
LED. Table 4.4 on page 4-13 explains the Remote I/O Scanner Mode LED.
The maximum number of:
If your remote I/O link: use this
resistor
rating:
physical
devices
connected on
the link:
racks that you
can scan on the
link:
operates at 230.4 K bits 82 32 16
operates at 57.6 or 115.2K bit/s, and no devices listed
below are linked:
Scanners: 1771-SN; 1772-SD, -SD2;
1775-SR, -S4A, -S4B;
Adapters 1771-AS; 1771-ASB (series A only);
1771-DCM
Miscellaneous 1771-AF
connects to any device listed below: 150 16 16
Scanners 1771-SN; 1772-SD, -SD2;
1775-SR, -S4A, -S4B;
Adapters 1771-AS; 1771-ASB (series A only);
1771-DCM
Miscellaneous 1771-AF
operates at 57.6 or 115.2K bit/s, and you do not require
over 16 physical devices
Table 4.2 DH+ Status LED
LED State Means
off channel not online
blinking green it is the only node on the network
solid green online and receiving token
blinking red duplicate node
solid red failed selftest