Rockwell-automation 20D DriveLogix Controller for PowerFlex 700S Phase Manuel d'utilisateur Page 16

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 18
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 15
16 DriveLogix Controller for PowerFlex 700S Phase I Drives
Monitoring the DriveLogix
Controller LEDs
!
ATTENTION: The controller LEDs are only operational when
the drive is energized, and only visible with the drive door open.
Servicing energized equipment can be hazardous. Severe injury
or death can result from electrical shock, burn or unintended
actuation of controlled equipment. Follow Safety related
practices of NFPA 70E, ELECTRICAL SAFETY FOR
EMPLOYEE WORKPLACES. DO NOT work alone on energized
equipment!
Type Name Color State Description
Daughter card
LEDs
PORT Green Status of DPI port internal communications (if
present).
MOD Yellow Status of communications module (when
installed).
NET A Red Status of network (if connected).
NET B Red Status of secondary network (if connected).
NET A OFF No power,
Host is faulted,
Host is holding daughter card in reset.
Red Steady Major Fault
Red Flashing Minor Fault
Green Flashing No connections established
Green Steady Connections established
NET B OFF No power,
Host is faulted,
Host is holding daughter card in reset.
Red Steady Major Fault
Red Flashing Minor Fault
Green Flashing No connections established
Green Steady Connections established