Rockwell-automation 1756-Lx_Mx ControlLogix Controller and Memory Boar Manuel d'utilisateur Page 42

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 52
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 41
42 ControlLogix Controller and Memory Board
Publication
1756-IN101L-EN-P - June 2008
ControlLogix Controller Common Specifications - 1756-L1, 1756-L1M1,
1756-L1M2, 1756-L1M3, 1756-L55, 1756-L55M12, 1756-L55M13, 1756-L55M14,
1756-L55M16, 1756-L55M22, 1756-L55M23, 1756-L55M24, 1756-L61, 1756-L62,
1756-L63, 1756-L64, and 1756-L65
Attribute Value
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0 … 60 °C (32…140 °F)
Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal
Shock):
-40… 85 °C (-40…185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% noncondensing
Vibration IEC60068-2-6 (Test Fc, Operating):
2 g @ 10…500 Hz
Shock, operating IEC60068-2-27 (Test Ea, Unpackaged Shock):
30 g
Shock, nonoperating IEC60068-2-27 (Test Ea, Unpackaged Shock):
50 g
Emissions CISPR 11:
Group 1, Class A
ESD immunity IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
Radiated RF immunity IEC 61000-4-3:
10V/M with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/M with 200 Hz 50% Pulse 100% AM at 900 Mhz
10V/M with 200 Hz 50% Pulse 100% AM at 1890 Mhz
1V/m with 1 kHz line-wave 80% AM from 2.0…2.7 GHz
EFT/B immunity IEC 61000-4-4:
±4 kV at 5 kHz on communications ports
Surge transient immunity IEC 61000-4-5:
±2 kV line earth (CM) on communications ports